85 FR 13 pg. 3232 - Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies

Type: RULEVolume: 85Number: 13Page: 3232
Docket number: [Docket Number EERE-2016-BT-STD-0022]
FR document: [FR Doc. C1-2019-26354 Filed 1-17-20; 8:45 am]
Agency: Energy Department
Official PDF Version:  PDF Version
Page: 3232

[top] page 3232

DEPARTMENT OF ENERGY

10 CFR Part 430

[Docket Number EERE-2016-BT-STD-0022]

RIN 1904-AD69

Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies

Correction

In rule document 2019-2635 beginning on page 1447 in the issue of Friday, January 10, 2020, make the following correction:

§?430.32 [Corrected]

On page 1503, in §?430.32(z)(3) the table should appear as follows:

Battery charger product class Rated output power Minimum efficiency
10a (VFD UPSs) 0 W < P rated = 300 W -1.20E-06 * P ? 2 rated + 7.17E-04 * P rated + 0.862.
300 W < P rated = 700 W -7.85E-08 * P ? 2 rated + 1.01E-04 * P rated + 0.946.
P rated > 700 W -7.23E-09 * P ? 2 rated + 7.52E-06 * P rated + 0.977.
10b (VI UPSs) 0 W < P rated = 300 W -1.20E-06 * P ? 2 rated + 7.19E-04 * P rated + 0.863.
300 W < P rated = 700 W -7.67E-08 * P ? 2 rated + 1.05E-04 * P rated + 0.947.
P rated > 700 W -4.62E-09 * P ? 2 rated + 8.54E-06 * P rated + 0.979.
10c (VFI UPSs) 0 W < P rated = 300 W -3.13E-06 * P ? 2 rated + 1.96E-03 * P rated + 0.543.
300 W < P rated = 700 W -2.60E-07 * P ? 2 rated + 3.65E-04 * P rated + 0.764.
P rated > 700 W -1.70E-08 * P ? 2 rated + 3.85E-05 * P rated + 0.876.

[FR Doc. C1-2019-26354 Filed 1-17-20; 8:45 am]