85 FR 13 pg. 3232 - Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies
Type: RULEVolume: 85Number: 13Page: 3232
Page: 3232Docket number: [Docket Number EERE-2016-BT-STD-0022]
FR document: [FR Doc. C1-2019-26354 Filed 1-17-20; 8:45 am]
Agency: Energy Department
Official PDF Version: PDF Version
[top]
DEPARTMENT OF ENERGY
10 CFR Part 430
[Docket Number EERE-2016-BT-STD-0022]
RIN 1904-AD69
Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies
Correction
In rule document 2019-2635 beginning on page 1447 in the issue of Friday, January 10, 2020, make the following correction:
§?430.32 [Corrected]
On page 1503, in §?430.32(z)(3) the table should appear as follows:
Battery charger product class | Rated output power | Minimum efficiency |
---|---|---|
10a (VFD UPSs) | 0 W < P rated = 300 W | -1.20E-06 * P ? 2 rated + 7.17E-04 * P rated + 0.862. |
300 W < P rated = 700 W | -7.85E-08 * P ? 2 rated + 1.01E-04 * P rated + 0.946. | |
P rated > 700 W | -7.23E-09 * P ? 2 rated + 7.52E-06 * P rated + 0.977. | |
10b (VI UPSs) | 0 W < P rated = 300 W | -1.20E-06 * P ? 2 rated + 7.19E-04 * P rated + 0.863. |
300 W < P rated = 700 W | -7.67E-08 * P ? 2 rated + 1.05E-04 * P rated + 0.947. | |
P rated > 700 W | -4.62E-09 * P ? 2 rated + 8.54E-06 * P rated + 0.979. | |
10c (VFI UPSs) | 0 W < P rated = 300 W | -3.13E-06 * P ? 2 rated + 1.96E-03 * P rated + 0.543. |
300 W < P rated = 700 W | -2.60E-07 * P ? 2 rated + 3.65E-04 * P rated + 0.764. | |
P rated > 700 W | -1.70E-08 * P ? 2 rated + 3.85E-05 * P rated + 0.876. |