79 FR 31 pgs. 8903-8904 - Energy Conservation Program: Energy Conservation Standards for Commercial and Industrial Electric Motors
Type: PRORULEVolume: 79Number: 31Pages: 8903 - 8904
Pages: 8903, 8904Docket number: [Docket Number EERE-2010-BT-STD-0027]
FR document: [FR Doc. C1-2013-28776 Filed 2-13-14; 8:45 am]
Agency: Energy Department
Official PDF Version: PDF Version
[top]
DEPARTMENT OF ENERGY
10 CFR Part 431
[Docket Number EERE-2010-BT-STD-0027]
RIN 1904-AC28
Energy Conservation Program: Energy Conservation Standards for Commercial and Industrial Electric Motors
Correction
In proposed rule document 2013-28776 appearing on pages 73589-73681 in the issue of Friday, December 6, 2013, make the following corrections:
1. On page 73594, Table I.5 should appear as set forth below:
Motor horsepower/standard kilowatt equivalent | Nominal full load efficiency (%) | 4 Pole | Enclosed | Open | 6 Pole | Enclosed | Open | 8 Pole | Enclosed | Open |
---|---|---|---|---|---|---|---|---|---|---|
1/.75 | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 | ||||
1.5/1.1 | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.0 | ||||
2/1.5 | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 | ||||
3/2.2 | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 | ||||
5/3.7 | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 | ||||
7.5/5.5 | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 | ||||
10/7.5 | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 | ||||
15/11 | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 | ||||
20/15 | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 | ||||
25/18.5 | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 | ||||
30/22 | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
2. On page 73627, Tables IV.10 and IV.11 should appear as follows:
Representative unit | EL 0 (EPACT 1992) (%) | EL 1 (NEMA premium) (%) | EL 2 (Best-in-market*) (%) | EL 3 (Max-tech) (%) |
---|---|---|---|---|
5 hp | 87.5 | 89.5 | 90.2 | 91.0 |
30 hp | 92.4 | 93.6 | 94.1 | 94.5 |
75 hp | 94.1 | 95.4 | 95.8 | 96.2 |
Representative unit | EL 1 (EPACT 1992) (%) | EL 2 (NEMA premium) (%) | EL 3 (Max-tech) (%) |
---|---|---|---|
5 hp | 87.5 | 89.5 | 91.0 |
50 hp | 92.4 | 93.6 | 94.5 |
[top]
3. On page 73634, in Table IV.14, In the second row, in the second column "1.61" Should read "51.61".
Representative unit | Per unit adder for 1 band above NEMA premium | Per unit adder for 2 bands above NEMA premium |
---|---|---|
5 HP, Design B | $11.06 | $17.36 |
30 HP, Design B | $32.89 | $51.61 |
75 HP, Design B | $66.18 | $103.86 |
5 HP, Design C | $10.68 | $16.75 |
50 HP, Design C | $60.59 | $95.08 |
§ 431.25 [AMENDED]
4. On page 73679, in § 431.25(d), Table 4 should appear as set forth below:
Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency | Open motors (number of poles) | 8 | 6 | 4 | 2 | Enclosed motors (number of poles) | 8 | 6 | 4 | 2 |
---|---|---|---|---|---|---|---|---|---|---|---|
250/186 | 94.5 | 95.4 | 95.4 | 94.5 | 94.5 | 95.0 | 95.0 | 95.4 | |||
300/224 | 95.4 | 95.4 | 95.0 | 95.0 | 95.4 | 95.4 | |||||
350/261 | 95.4 | 95.4 | 95.0 | 95.0 | 95.4 | 95.4 | |||||
400/298 | 95.4 | 95.4 | 95.4 | 95.4 | |||||||
450/336 | 95.8 | 95.8 | 95.4 | 95.4 | |||||||
500/373 | 95.8 | 95.8 | 95.8 | 95.4 |
[FR Doc. C1-2013-28776 Filed 2-13-14; 8:45 am]